GFTCB230 is Eaton’s 30A two-pole Type BR GFCI breaker. It provides personnel ground-fault protection together with common-trip overcurrent protection on a 120/240V circuit and carries a 10 kAIC interrupt rating.
GFTCB230 specifications
-
Eaton catalog number: GFTCB230
-
Family: Type BR / GFTCB
-
Function: Ground-fault circuit interrupter
-
Rating: 30A, 2 pole, 120/240V AC
-
Trip: Common trip
-
Interrupt rating: 10 kAIC
-
Wire range: #14–4 AWG
-
Standards: UL 943 and UL 489
-
Neutral: Factory pigtail configuration
What is verified—and what is not claimed
Eaton’s current product record still identifies GFTCB230 by this exact catalog number. The previous copied copy called it discontinued and assigned a replacement without a supporting manufacturer status, so that statement has been removed. This is GFCI-only, not an AFCI/GFCI dual-function breaker.
Check Type BR approval and circuit details
Confirm the loadcenter label permits GFTCB breakers and match 30A, two poles, 120/240V, GFCI function, conductor range, and 10 kAIC. Follow the Eaton wiring diagram for line and load neutral connections. A qualified person should verify the load, panel, and installation.